#210 – Explaining Sidewall Sprinkler Heads, Both Horizontal and Vertical

Last updated on

Jason Hugo
Founder & CEO
Jason Hugo

Slight differences between two less-common fire sprinkler types give designers and installers much-needed flexibility

There are plenty of good reasons why most fire sprinklers are mounted in pipes above or just below ceilings, including:

  • Fire sprinklers are heat-activated, and heat rises
  • Higher sprinklers can cover wider areas
  • For the most part, heads placed near the ceiling face fewer obstructions (like furniture, cabinets, and other large objects) that might get in the way

But there are also good reasons to mount sprinklers along walls—and plenty of ways to do it, too, thanks to the sidewall sprinkler head. In this article, we look at what these fire sprinklers do and how horizontal and vertical models play slightly different roles in active fire protection.

Not interested in the finer points of sidewall sprinkler heads? Browse our full selection of sidewall sprinklers.

Sidewall sprinkler heads go where pendent and upright sprinklers can’t (or shouldn’t)

We’ve explained much of what separates one kind of fire sprinkler head from another in our in-depth look at fire sprinkler head types. But basically, each sprinkler is designed to point in a direction. Pendent sprinklers (the most common type) point downward and to the sides from a ceiling or beam. Horizontal sidewall sprinklers, on the other hand, install horizontally, often in a wall. They may or may not stick out, depending on the sprinkler’s construction and the way it’s mounted, but each of these heads relies on piping along or behind a wall for a supply of water.

There are two big reasons to use sidewall sprinklers:

  • Access to ceiling piping is limited or unavailable
  • Ceiling-mounted sprinkler heads would somehow detract from the building’s aesthetics

By and large, most sidewall sprinkler heads are horizontal sidewall sprinklers. They’re designed to point parallel to the floor.

Horizontal sidewall sprinklers installed in a wall
The white sprinklers along this decorative trim just under the ceiling take advantage of pipes concealed within the walls. Image source: A.L. Fire Protection

However, most sprinkler manufacturers also offer vertical sidewall sprinklers. These heads point perpendicular to the floor and can be installed either facing up (a classic upright orientation) or down (a classic pendent orientation). That flexibility makes them unusual. Upright and pendent sprinklers, for example, can face only one way—and will likely fail to keep a fire in check if installers choose the wrong orientation.

A window fire sprinkler
Specialized vertical sidewall models point water to specifically cool interior glass when a fire strikes, eliminating the need for fire-rated glass.

A short sidewall case study: apartment fire protection

For a great example of when these sprinklers do what others can’t, let’s watch one in action:

This isn’t a typical use, as sidewalls are usually indoors. Residential buildings like hotels use the lion’s share of sidewall sprinklers, and they’re also common in dining rooms, offices, and other spaces where running overhead pipe is impractical or ceiling aesthetics are a high priority.

But the design in the video—which features a horizontal sidewall head placed beneath an outdoor walkway on an apartment complex—embodies many of the benefits offered by sidewall heads. Neither upright nor pendent sprinklers make much sense here, for several reasons:

  • Running pipe for pendent sprinklers in the outside wooden deck is impractical.
  • This configuration connects an outdoor sprinkler to protected, climate-controlled indoor pipes, reducing the risks of vandalism, impact, and freezing.
  • The sidewall is used “For the protection of exterior projections and similar structures,” one of NFPA 13’s nine permitted use cases.

Sidewall sprinklers do have certain limits (as we’ll see in the next section). Still, as an alternative to pendent or upright heads, they support designs that work where other orientations wouldn’t.

Vertical and horizontal sidewall sprinkler models look similar but are easily distinguished by their deflectors

To tell a sidewall sprinkler head from another type, look at the deflector. These small plates rest between the sprinkler’s orifice and the space it protects, shaping the water pattern as it sprays. While most (upright and pendent) sprinklers have a spoked circle, sidewall heads have a deflector that usually combines a semicircle and a flat plate that runs perpendicular to it. That shape guides water away from one direction and toward the intended direction.

Victaulic v2709 fire sprinkler
Not all deflectors look exactly like this, but Victaulic’s V2709 head has a style common to horizontal sidewall heads.

The deflector holds the key to telling these sprinklers apart—and to installing them properly. Horizontal models are marked with the word “top,” indicating the side of the deflector that should face the ceiling. In contrast, vertical models feature an arrow and the word “flow.”

Flow label on a sidewall sprinkler
Deflectors on all modern fire sprinklers are stamped with need-to-know information. Among other things, these stamps, like “Flow” and “Top” above, tell installers which direction heads like these should face.

Horizontal and vertical models have slightly different installation requirements

In 1996, professor and fire protection engineer Glenn Corbett described sidewalls—with more than a trace of irony—as “superhuman” sprinkler heads. His article for Fire Engineering drew attention to a concerning trend in fire protection to install sidewall sprinklers in ways that simply weren’t safe. Installers, he said, often overestimated their abilities, placing them too close to obstacles or otherwise putting them in places that don’t work.

That’s a big problem, and for a simple reason: like other fire sprinkler types, sidewall heads activate when they get hot. But tests have shown that some parts of buildings—particularly, those where a wall and ceiling meet—manage to lock cooler pockets of air in place. This phenomenon, called “dead air,” can cause heads to start spraying too late, allowing a fire to spread.

Diagram of smoke detector installation
This illustration shows smoke detectors and the dead space nearby—but the principle is the same for sidewall sprinklers, which won’t work properly if placed in dead air space. Image source: Drewprops

As such, sidewalls and other heads need clearance from dead air. The 2022 edition of NFPA 13: Standard for the Installation of Sprinkler Systems requires the following clearances for vertical and horizontal sidewall sprinklers:

  • At least four inches of clearance between deflectors and ceilings or end walls for all models
  • No more than six inches of clearance from the ceiling for vertical sidewall models only
  • No more than 18 inches of ceiling clearance for horizontal sidewall models specifically listed for that use, when placed below non-combustible and limited-combustible ceilings
  • No more than six inches of ceiling clearance for all other horizontal-type models

NFPA 13 also prescribes a minimum distance from the deflector to the wall where the sprinkler is installed:

  • Vertical models: four to six inches
  • Horizontal models: zero to six inches
Viking concealed sidewall sprinkler
Behind the white disc (cover plate) on this Viking VK4800 is a fully-functional residential horizontal sidewall sprinkler.

With globally recognized manufacturers competing for a share of the fire protection market, sidewall sprinkler purchasers have a wide array of options

Sidewall sprinklers open up design possibilities in a wide variety of buildings. They’re certainly not “superhuman”—but they’re an impressive and helpful addition to any designer’s toolkit.

QRFS carries more than 40 sidewall sprinkler models from industry-leading manufacturers Victaulic, Viking, Senju Sprinkler, and Tyco. With a variety of temperatures, finishes, and orifice sizes for residential and commercial heads—both quick and standard response—our selection has sprinkler heads suited to almost any project.

Viking VK305 sidewall fire sprinkler
QRFS has commercial sidewall heads rated for temperatures including 286 degrees Fahrenheit, 200 degrees, and 155-degree models like this Viking VK305.

All of our residential models are UL-listed and ready for installation in NFPA 13D and 13R fire sprinkler systems. Each of our commercial models is UL-listed, FM-approved, and ready for installation in NFPA 13-compliant systems.

Senju flush horizontal sprinkler.
Our line of horizontal heads includes Senju’s decorative flush sidewall sprinklers for residential buildings, which offer a balance of aesthetics and function.

Browse our selection of sidewall sprinklers.

Questions about sidewall sprinklers? Call us at +1 (888) 361-6662 or email support@qrfs.com.

This blog was originally posted at blog.qrfs.com. If this article answered your questions about these useful heads, check us out at Facebook.com/QuickResponseFireSupply or on Twitter @QuickResponseFS.

The material presented on QRFS.com and the QRFS Blog, including all text, images, graphics, and other information, is presented for promotional and informational purposes only. Every circumstance has its unique risk profile and must be assessed individually. The content on this website in no way eliminates the need for assessments and advice from a life safety or fire protection professional, the services of which should be employed in all situations. In addition, always consult with a professional, such as a life safety engineer, contractor, and your local authority having jurisdiction (AHJ; a fire marshal or other government official) before making any changes to your fire protection or life safety system.
Jason Hugo
Written by Jason Hugo
Founder & CEO

Jason Hugo is the founder and CEO of Quick Response Fire Supply. After working for a sprinkler manufacturer, he launched QRFS in 2010 to solve the difficulties he saw customers face because they lacked easy access to fire protection parts and information. Jason is dedicated to providing building owners, facility managers, and fire protection professionals with resources that help keep people safe and fire protection systems compliant.

Thoughts on Fire Comment Policy:
QRFS appreciates your fire protection questions. In this forum, we answer clearly phrased questions we can answer with reasonable effort and knowledge. We also answer QRFS-product-specific questions or escalate them to our customer service team. However, we may not answer questions related to unique system designs, complex code interpretations, or ones that require gathering significant information about a system. In these cases, individuals should consult a local fire protection professional.