My Sprinkler Gauges Are Expired—What Do I Do?

Last updated on

Jason Hugo
Founder & CEO
Jason Hugo

The problem

Fire sprinkler systems rely on accurate pressure readings to ensure everything works as designed during a fire. But sprinkler gauges don’t last forever. They must either be replaced or tested every five years—and potentially be recalibrated or replaced after the test.

If gauges are expired, their readings may be incorrect, potentially compromising system performance when it matters most. Out-of-date gauges can also trigger a deficiency tag during inspection, leading to extra costs and inconvenience.

Why this matters

NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems sets specific requirements for gauge maintenance, because malfunctioning gauges can lead to incorrect system pressure readings—and sprinkler systems that fail in a fire.

13.2.4.2* Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

13.2.4.3 Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced. [NFPA 25: 2023]

Many people ask, “Do I need to do this five years after installation or five years after the gauge was manufactured?” Recent editions of NFPA 25 aren’t particularly clear on this, but the 2014 edition of the NFPA 25 Handbook was:

The 5-year period is based on the installed date as opposed to the manufacture date of a gauge, so it is acceptable to mark the installed date with a permanent marker on a label or on the body of a gauge when it is originally installed or calibrated.

In any case, expired gauges not only may result in inaccurate pressure readings; they can also lead to a system deficiency tag during your next inspection!

The fix

To stay compliant and safe, building owners need to either test or replace expired sprinkler gauges:

Option 1: Testing

A fire protection pro obtains a verifiably calibrated test gauge, inserts it into a system connection (ideally, a dedicated gauge test valve), and takes pressure readings. Then, the process is repeated for each system gauge to be tested, and the subsequent readings on the system gauges are compared to the calibrated test gauge.

If the reading on any gauge is not “within 3 percent of the full scale,” it must be recalibrated or replaced. Testing can be costly and inconvenient, especially if recalibration or replacement is still required afterward.

Option 2: Replacement

Many owners skip testing and simply replace gauges outright—often, an efficient move, as new gauges are affordable and readily available. NFPA 25 acknowledges this approach, stating, “In many cases, replacement might be more economical than testing.”

Buyer’s guide

Choosing a sprinkler gauge involves several considerations:

  • System type & pressure: Match the gauge to your system type and what it’s measuring (air or water) and the necessary pressure range—QRFS gauges span from -30 to 300 PSI.
  • Accuracy: Choose gauges with at least ±3/2/3% range-based accuracy.
  • Certifications: UL Listed or FM Approved gauges are not required by NFPA standards, but these “listings” indicate high quality.

Need help? Contact QRFS.

Product recommendations

Find sprinkler gauges & more at QRFS

If you need fire protection parts, check out our selection of:

Have questions or need help placing an order? Contact us!

FAQs

When does the 5-year replacement period start—at manufacture or installation?

It starts at installation, though it’s not necessarily a bad idea to replace unused gauges that have been sitting unused in a box for many years.

Can I test my sprinkler gauge instead of replacing it?

Yes, but testing requires employing a professional who uses a calibrated test gauge to conduct a comparison process with each gauge that’s assessed. And if a gauge is off by 3% or more, it must still be recalibrated or replaced. It’s usually simpler to just buy new ones.

What happens if my gauges are expired?

Your system may be tagged with a deficiency during inspection, and the system pressure readings may not be reliable, potentially leading to problems during an emergency.

Do I need a listed gauge?

NFPA 13 doesn’t require “listed” gauges, instead stating they must only be “approved” [by the authority having jurisdiction]. However, UL Listed or FM Approved gauges (either one counts as a “listing” to NFPA) are a strong sign of product quality.

How to Protect Gauges from Overpressure and Damage

Pressure spikes can damage gauges. Prevent gauge overpressure damage by understanding ratings…

Sprinkler Gauges: Know Your Fire Sprinkler System is Ready for Action

Fire sprinkler gauges – air or water pressure gauges installed at various points throughout the…

Ashcroft Gauges: Setting the Standard in Fire Protection and Testing

Ashcroft Gauges have set the standard for Fire Protection and Testing for over a century. Learn…
The material presented on QRFS.com and the QRFS Blog, including all text, images, graphics, and other information, is presented for promotional and informational purposes only. Every circumstance has its unique risk profile and must be assessed individually. The content on this website in no way eliminates the need for assessments and advice from a life safety or fire protection professional, the services of which should be employed in all situations. In addition, always consult with a professional, such as a life safety engineer, contractor, and your local authority having jurisdiction (AHJ; a fire marshal or other government official) before making any changes to your fire protection or life safety system.
Jason Hugo
Written by Jason Hugo
Founder & CEO

Jason Hugo is the founder and CEO of Quick Response Fire Supply. After working for a sprinkler manufacturer, he launched QRFS in 2010 to solve the difficulties he saw customers face because they lacked easy access to fire protection parts and information. Jason is dedicated to providing building owners, facility managers, and fire protection professionals with resources that help keep people safe and fire protection systems compliant.

Thoughts on Fire Comment Policy:
QRFS appreciates your fire protection questions. In this forum, we answer clearly phrased questions we can answer with reasonable effort and knowledge. We also answer QRFS-product-specific questions or escalate them to our customer service team. However, we may not answer questions related to unique system designs, complex code interpretations, or ones that require gathering significant information about a system. In these cases, individuals should consult a local fire protection professional.