How Do I Winterize My Dry Fire Sprinkler System?

Last updated on

Jason Hugo
Founder & CEO
Jason Hugo

The problem

Dry pipe sprinkler systems are built for cold environments—but they’re not immune to the effects of freezing. Even though most of the system’s pipe network contains pressurized air or nitrogen, small amounts of water can still collect from things like condensation or system activation, whether the latter is from testing or a fire.

If you don’t complete proper winterization steps before temperatures drop, any trapped or leftover water freezes. When it does, it can cause significant damage, leading to costly repairs. The system will also be out of compliance with codes and standards, and worse, it may fail to control a fire.

Why this matters

NFPA 25 requires building owners to take action before and during freezing conditions to keep systems operational and compliant. Again, even in dry systems, certain components still contain water and must be protected from freezing.

Failure to meet these requirements can result in blocked sprinklers and pipes, damaged pipes and leaks, system failure during a fire event, and deficiencies after an inspection. Sufficient freeze damage could even trigger leaks that cause an unintentional system activation.

These aren’t theoretical risks—they directly impact whether your system is code-compliant—and will work when it’s needed.

The fix

NFPA 25 outlines the required inspection, testing, and maintenance (ITM) steps to prepare dry fire sprinkler systems before freezing weather and ensure they work during it. The items below aren’t everything—ITM pros will do additional work—but they are the essentials.

The first rule is something that applies to all system types:

The property owner or designated representative shall ensure that water-filled piping that is subject to freezing is maintained at a minimum temperature of 40°F (4°C) (NFPA 25, 2026: 4.1.2).

This doesn’t apply to most of a dry system. However, the dry pipe valve, control valve, some pipe, and other equipment near the water supply are in a protected “valve enclosure” (sometimes called a “valve room”) that must remain heated. This creates specific inspection and testing requirements:

  • Ensure all valve enclosures are maintained above 40°F (4°C) during winter, inspecting them:
    • Daily, if no low-temperature alarm is installed (4.1.2.5)
    • Weekly, if a low-temperature alarm is installed (4.1.2.5.1)
  • If you have low-temperature alarms, they must be inspected annually for damage “toward the beginning of the heating season” (4.1.2.5.2).
  • Test low-temperature alarms annually “toward the beginning of the heating season” (13.4.5.2.7). On older alarms, a fire protection pro may expose the temperature-sensing element to a lower temperature using an ice bath or a spray. Newer models have self-testing or software-based options.

There are also annual testing requirements for the dry pipe valve:

  • Ensure a fire protection ITM pro trip-tests the dry pipe valve annually “during warm weather (13.4.5.2.2*).”
    • The annual requirement is a partial test, during which water flows only to a limited area near the dry pipe valve (13.4.5.2.2.3).
    • Every three years, this must be a full trip test that floods the entire system (13.4.5.2.2.2).

In addition, the essential winterization requirements include proper drainage:

  • Drain all auxiliary drains “toward the beginning of the heating season prior to the onset of freezing conditions (13.4.5.3.3).” Auxiliary drains release water from “trapped” sections of pipe that won’t flow to the main drain.
  • Ensure signage is present “at the dry valve indicating the number of auxiliary drains and the location of each individual drain (13.4.5.1.1).” This helps ensure no trapped sections of pipe are missed.

Completing these winterization steps—including verifying that a fire protection pro otherwise fully services the system—is vital for achieving compliant, protected, and working dry systems.

Product recommendations

FAQs

When should I winterize my dry pipe system?

Before the onset of freezing conditions, typically at the beginning of the heating season. Some of NFPA 25’s annual requirements for these systems don’t specify when to do them; however, scheduling a pro to do everything at once before winter is efficient.

Why are auxiliary drains so important?

They remove trapped water that can freeze and damage pipes or block system operation. The pipes in dry systems are pitched so that water drains easily from the system. However, some sections of pipe are laid out in a way that can prevent that water from exiting without auxiliary drains.

Why do dry fire sprinkler systems still contain some water?

Systems need to access a water supply, so water will necessarily be present in the valve enclosure area. It can also collect due to condensation, testing, or system activation, intentional during a fire or otherwise.

Fire Sprinkler System Freeze Prevention: Ball Valves, Drum Drips & More

Antifreeze isn’t always the best—or the only—approach to fire sprinkler system freeze prevention…

Guide to Dry Sprinkler Systems, Part 10: Trip Testing the Dry Pipe Valve

Learn the steps, components, and key considerations involved in dry pipe sprinkler system trip tests…

Guide to Dry Sprinkler Systems, Part 6: Quarterly, Annual, and Longer Inspections

QRFS finishes its thorough guide to meeting NFPA 25 timelines for dry sprinkler system inspections…

Draining a Fire Sprinkler System: Main Drain, Auxiliary Drain, and More!

Why would a fire protection system need to be drained? This article discusses four common reasons…
The material presented on QRFS.com and the QRFS Blog, including all text, images, graphics, and other information, is presented for promotional and informational purposes only. Every circumstance has its unique risk profile and must be assessed individually. The content on this website in no way eliminates the need for assessments and advice from a life safety or fire protection professional, the services of which should be employed in all situations. In addition, always consult with a professional, such as a life safety engineer, contractor, and your local authority having jurisdiction (AHJ; a fire marshal or other government official) before making any changes to your fire protection or life safety system.
Jason Hugo
Written by Jason Hugo
Founder & CEO

Jason Hugo is the founder and CEO of Quick Response Fire Supply. After working for a sprinkler manufacturer, he launched QRFS in 2010 to solve the difficulties he saw customers face because they lacked easy access to fire protection parts and information. Jason is dedicated to providing building owners, facility managers, and fire protection professionals with resources that help keep people safe and fire protection systems compliant.

Thoughts on Fire Comment Policy:
QRFS appreciates your fire protection questions. In this forum, we answer clearly phrased questions we can answer with reasonable effort and knowledge. We also answer QRFS-product-specific questions or escalate them to our customer service team. However, we may not answer questions related to unique system designs, complex code interpretations, or ones that require gathering significant information about a system. In these cases, individuals should consult a local fire protection professional.