How to Stop a Fire Sprinkler Head with the Correct Shutgun Sprinkler Tool

Last updated on

Jason Hugo
Founder & CEO
Jason Hugo

Fire sprinkler shutoff tools minimize the risk of water damage but there’s no one-size-fits-all solution

Compared to fire hoses, fire sprinklers ration water exceptionally well, containing or stopping fires with significantly less water—anywhere from 50 percent to nearly 95 percent less. But when a fire sprinkler accidentally discharges with no fire in sight, water damage (and the resulting expenses of cleanup) can amass quickly. The Shutgun is the solution.

This specialized line of tools can allow anyone—even those with a flimsy understanding of how fire sprinklers work—to stop sprinkler discharge. In this article, we explain what these fire sprinkler shutoff tools do, how they vary, and how everyone, from building owners to contractors, can make an informed purchase of the right one for the job.

Readers familiar with the Shutgun are invited to browse our selection of fire sprinkler shutoff tools—click here.

Fire sprinkler shutoff tools aren’t the only way to stop discharge from a broken head—but they may be the fastest

In “How to Temporarily Stop a Damaged or Activated Fire Sprinkler Head,” QRFS looked at a range of situations leading to unwanted fire sprinkler activation. In short, fire sprinklers almost never discharge from a manufacturing defect but human error—from actions as simple as hanging a wedding dress on a sprinkler head—can unleash a damaging deluge of water. Tens of thousands of dollars have been spent repairing damage in college dormitories, hotels, detention centers, and any other setting where fire sprinklers and people are in close quarters.

It should be fairly easy to stop an accidental discharge. Each building should have designated personnel who can quickly locate and operate shut-off valves, either in the area affected or (if needed) for the whole system.

Fire sprinkler control valve
While control valves can stop additional water from entering pipes, water will continue to drain through open heads—and the heads downstream of the valve will be rendered inactive. This one is chained in the open position—and not everyone has the key, of course. Source: Dan Keck via Flickr

That’s the theory, anyway—but the practice is a bit more complicated. If, for some reason, there’s nobody familiar with the fire sprinkler system on-site (or if the facility only allows select personnel to interact with control valves) locating and using those valves becomes far more difficult. On-site staff may need to contact the fire department and wait until they show up to shut the valves themselves. In the meantime, water damage continues. Some restoration firms estimate that a fire sprinkler causes $1,000 to $2,000 in damage each minute it remains active.

Afterward, the headache isn’t over: water still in the system will continue to drain through the open head. And closing those control valves has left the fire sprinkler system inactive, in part or in whole, placing the building at risk in the event of a fire. Consequently, local fire codes may require people to patrol the building day and night watching for fire or, in some cases, occupants to evacuate the building until sprinkler contractors complete repairs.

Looking for a more extensive introduction to accidental discharge and its prevention? Click here.

The Shutgun stops fire sprinklers from discharging water—while temporarily acting as a new sprinkler head

In most instances, unwanted discharge is localized. Sprinkler heads in the vast majority of systems activate one at a time, which means that stopping water damage is ultimately a matter of finding and closing off a single damaged head.

Enter the Shutgun: a sprinkler tool designed to stop water from individual heads, one at a time. Developed by Technicraft, a Canadian manufacturer of leak-prevention tools, it not only closes off the damaged fire sprinkler, but it also acts as a substitute for its thermal element and plug—the parts that fall away when a head activates. To stop the flow of water, users place the tool’s tip at the orifice and squeeze the handle. That squeezing motion spreads its jaws apart, leaving the Shutgun securely fastened to the sprinkler’s frame with the orifice completely sealed.

A concealed Shutgun in use
This photograph shows Shutgun closing off a concealed sprinkler head. As we’ll see shortly, different head types require different fire sprinkler shutoff tools. For example, concealed fire sprinklers require a specific model.

Each Shutgun sprinkler tool acts as a short-term replacement for a fire sprinkler head. If ambient temperatures get too high (typically, over 165 degrees Fahrenheit), the tool detaches from the sprinkler, allowing water to flow just as it would if the sprinkler activated normally.

Fire sprinklers vary; so does this shutoff tool

Many fire sprinklers can be fixed with the standard Shutgun, which stops spray from pendent, horizontal sidewall, and upright-type heads. Each of these types is readily identifiable by how it hangs: pendent sprinklers point downward, upright heads point up, and horizontal sidewall heads stick out from a wall or exposed, vertically running pipe. Standard Shutguns are designed to work with sprinklers that have a 1/2-inch orifice—the most common size.

Need a primer on fire sprinkler types? Click here.

 

Pendent, upright, and sidewall fire sprinklers
Fire sprinkler heads, from left to right: pendent (hanging), upright, and horizontal sidewall. In most cases, a standard Shutgun sprinkler tool can stop the flow of water from all three types.

Two sprinkler types can’t be shut off with a standard model: concealed heads, which sit too deep for the tip to reach, and institutional heads, which have an unusual design that can’t be gripped with the jaws of a conventional Shutgun. Conventional models also won’t work when heads have been so damaged that parts of the frame are missing.

But in each of these cases, specialty fire sprinkler shutoff tools can provide quick and easy closure. For concealed heads, there’s a concealed Shutgun; for institutional heads, an institutional model; and, for sheared heads, there’s—you guessed it—a sheared model.

A few simple tips to help building owners reduce water damage with fire sprinkler shutoff tools

In a large building, it can be difficult to determine which Shutgun (or several models) are needed. Pendent sprinkler heads tend to be the most common, but many buildings use a mix of sprinkler types. Hotels, for example, may have concealed sprinklers in areas where appearances matter—such as bedrooms and common areas—along with standard pendents in non-guest areas and sidewall sprinklers in hallways.

However, there’s an alternative to scouring every floor and ceiling for sprinkler head types. In jurisdictions that adopt guidelines from the National Fire Protection Association (NFPA), all commercial buildings (and large residential buildings) must have a supply of spare sprinkler heads on hand. These rules, which are listed in NFPA 13: Standard for the Installation of Sprinkler Systems, stipulate that those spare sprinklers be kept in a cabinet on the premises.

Spare fire sprinkler cabinet
Along with spare heads and their wrenches, NFPA-13-compliant sprinkler cabinets feature a list of sprinklers installed on the premises.

Not only does this cabinet need to provide spares for every sprinkler—providing a solid indication of which types are in use—it also includes a full list of sprinklers installed on the property. While they don’t say how many of a given type are in use, or where they’re located, complete lists provide basic descriptions of each sprinkler model, including their type or orientation. That list can be used to determine which Shutgun models are needed.

Two additional recommendations can help minimize water damage: first, ensure that fire sprinkler shutoff tools are accessible, easy to find, and close at hand. To fully reap the benefits of owning a Shutgun, it’s important to have one within walking distance on every floor—otherwise, it’s not necessarily faster than running to the control valve. Second, if the building features a dense mix of sprinkler types, give some thought to the Shutgun Kit, which includes all four models along with additional attachments for concealed heads, sheared heads, and large heads.

Full kits allow contractors to confidently face uncertain risks

While building owners and property managers have the time and access needed to plan against accidental discharge, construction workers may know little to nothing about the fire sprinkler system in a given building. Contractors working around sprinklers may find themselves unable to answer basic questions when one is accidentally opened: who’s responsible for shutting the water off? Where’s the control valve? Do I have to call the fire department?

A missing control valve sign in a fire sprinkler system
Missing signage on control valves can compound the woes facing contractors when a sprinkler accidentally activates. Source: Fire Protection Deficiencies

While it’s tempting to pre-emptively shut the system down, that’s not an option in many cases. During renovations, a shut-down may require a costly fire watch. And while keeping a Shutgun handy is a solution, there’s another issue: fire sprinklers vary from job site to job site. Which model do you choose?

A standard model may help most contractors in most cases, but it’s not always ideal. If the work involves placing heavy machinery, pipe, or other materials near fire sprinklers, a sheared Shutgun may deliver when a standard version can’t. Contractors may be able to infer which kinds of sprinklers are likely in a given facility—systems in low-temperature environments often feature ice-resistant upright heads, while correctional facilities and hospitals frequently use tamper-resistant institutional heads—but that sort of guesswork can prove expensive.

This is why most contractors are probably best served by the Shutgun Kit. Its attachments for a variety of scenarios and sprinkler types allows contractors to work on a range of job sites with the knowledge that nearly any sprinkler can be closed off in a matter of seconds.

Simple preparations can keep accidental sprinkler discharge in check

With options for concealed heads, sheared heads, institutional heads, and standard upright or pendent heads, Technicraft’s line of Shutguns make quick work of getting rogue fire sprinklers under control. They’re surprisingly easy to use but it’s important for users to familiarize themselves with how they work before the situation calls for it. Few learning experiences are as close to “drinking from a fire hose” as stopping an actively-discharging sprinkler head. But as the video below shows, using these tools is easy enough:

QRFS is proud to offer four of Technicraft’s leading fire sprinkler shutoff tools, including:

Each of them is made from cast aluminum and features a heat-sensitive metal element that detaches at 165 degrees Fahrenheit, allowing damaged sprinklers to continue providing fire protection.

QRFS also offers Technicraft’s Shutgun Kit, which includes the following items in a portable carrying case weighing only six pounds:

  • Four Shutguns, including the original, sheared, institutional, and concealed models
  • One additional concealed head tip for ¾” sprinkler heads
  • Two additional sheared head attachments—one for ½” and one for ¾” sprinkler heads
  • One attachment for 3/4″ fire sprinkler heads
Shutgun sprinkler tool kit
Minimize risks with a full Shutgun Kit backed by Technicraft’s one-year warranty.

Browse our selection of Shutgun sprinkler tools and accessories.

Questions about fire sprinkler shutoff? Call us at +1 (888) 361-6662 or email support@qrfs.com.

This blog was originally posted at blog.qrfs.com. 

The material presented on QRFS.com and the QRFS Blog, including all text, images, graphics, and other information, is presented for promotional and informational purposes only. Every circumstance has its unique risk profile and must be assessed individually. The content on this website in no way eliminates the need for assessments and advice from a life safety or fire protection professional, the services of which should be employed in all situations. In addition, always consult with a professional, such as a life safety engineer, contractor, and your local authority having jurisdiction (AHJ; a fire marshal or other government official) before making any changes to your fire protection or life safety system.
Jason Hugo
Written by Jason Hugo
Founder & CEO

Jason Hugo is the founder and CEO of Quick Response Fire Supply. After working for a sprinkler manufacturer, he launched QRFS in 2010 to solve the difficulties he saw customers face because they lacked easy access to fire protection parts and information. Jason is dedicated to providing building owners, facility managers, and fire protection professionals with resources that help keep people safe and fire protection systems compliant.

Thoughts on Fire Comment Policy:
QRFS appreciates your fire protection questions. In this forum, we answer clearly phrased questions we can answer with reasonable effort and knowledge. We also answer QRFS-product-specific questions or escalate them to our customer service team. However, we may not answer questions related to unique system designs, complex code interpretations, or ones that require gathering significant information about a system. In these cases, individuals should consult a local fire protection professional.